Turbo-Bar™ Insertion Turbine Flow Meter
»Features »Specifications »Installation »Model Codes
 
    
»View Demo
»Documentation
Turbo-Bar
»Technology

EMCO's Turbo-Bar™ flow meter provides significant cost savings for line sizes from 3 to 80" without compromising performance. With high accuracy, wide turndown, and a unique low-mass rotor design without welded joints, the Turbo-Bar™ flow meter gives you the benefit of over 30 years of practical experience. The Turbo-Bar™ measures liquids or gases, including steam, for pipe sizes from 3 to 80".









Features
Unparalleled Performance
  • ± 1.0% of rate accuracy
  • ± 0.25% of rate repeatability
  • ± Turndown ratio up to 35:1
  • FM approval
  • Calibration is traceable to NIST
Significant Cost Savings
  • One Turbo-Bar™ flow meter is suitable for pipe sizes 3 to 80", so there is one purchase price, regardless of pipe size, resulting in typical savings of up to 80% for 24" lines and 50% for 10" lines compared to full-bore flowmeters
  • Installed quickly and easily, saving as much as 70% in labor installation costs when compared to full-bore flow meters
  • Hot-tap-compatible installation allows removal without process shutdown; this not only avoids disruption of a critical process, but also reduces labor costs
  • Negligible pressure drop, typically 10 times less than an orifice plate, reduces energy and operating costs
  • Unique low-mass rotor design is fabricated from one solid block of stainless steel, with no welded joints, maximizing rotor longevity and increasing sensitivity to changes in flow
  • Optional integral pressure and temperature measurement enables mass flow measurement from one pipe tap (installation)
Ease of Operation
  • Factory calibrated and programmed for specific applications
  • Start-up without any additional calibration or programming
  • EZ-Logic™ local display alternates between flow rate and totalized flow
  • Menu-driven EZ-Logic™ user interface enables local programming
  • HART® communication protocol

Back to top

Specifications
Performance Specifications
Accuracy
(linear ranges)
L1, G1-G5 ±1.0% of flow rate
G6 Rotor ±3.0% of flow rate
Repeatability ± 0.25% of flow rate

Back to top

Operating Specifications
Fluid types Liquid, gas, or steam
Measurable flow velocities see Rotor Selection Guide below
Process measurement TMP-600/60S 125 psi (8.62 barg)    Line Sizes 3-20"
TMP-700 5000 psi (1345 barg)    Line Sizes 3-80"
TMP-910/960 According to flange rating, up to 1500 psi    Line Sizes 3-80"
Process temperature limit TMP-600/60S 400°F (204°C) max
TMP-700 600°F (316°C) max
TMP-910/960 750°F (400°C) max
Ambient temperature limit EZ-Logic electronics 32 to 140°F (0 to 60°C)
All other electronics -20 to 140 °F (-40 to 60 °C)
Ambient humidity limit Up to 100% RH non-condensing
Power requirements EZ-Logic electronics 18 to 40 VDC, 24 VDC nominal
All other electronics 15 to 40 VDC, 24 VDC nominal
Output signals EZ-Logic electronics 4 to 20 mA analog and frequency/pulse outputs and local rate and total display

Back to top

Rotor Selection Guide
Liquid minimum and maximum flow rates
Rotor Pipe size " (mm) 3-5"
(80-125)
6"
(150)
8"+
(200+)
L1 (ft/sec) Vmax
Vlin
Vmin
30
1.4
0.5
30
1.5
0.6
30
1.46
0.7
(m/sec) Vmax
Vlin
Vmin
9
0.4
0.2
9
0.5
0.2
9
0.5
0.2
Rotor All sizes 3-5" 6" 8"+
Vmax Vlin Vmin Vlin Vmin Vlin Vmin
G1
40° Pitch
55 3.19/ 1.94/ 2.00/ 1.23/ 1.50/ 1.00/
G2
30° Pitch
70 3.98/ 2.26/ 2.27/ 1.63/ 1.90/ 1.31/
G3
20° Pitch
85 4.52/ 2.42/ 2.52/ 1.95/ 2.18/ 1.40/
G4
15° Pitch
115 5.84/ 3.85/ 3.78/ 2.84/ 3.00/ 2.19/
G5
10° Pitch
145 6.91/ 4.57/ 4.78/ 3.47/ 3.54/ 2.81/
G6
5° Pitch
175 6.10/ N/A 5.53/ N/A 5.00/ N/A
Gas or Steam Minimum and Maximum Velocity Rates (m/s)
Rotor All sizes 80-125 mm 150 mm 200mm +
Vmax Vlin Vmin Vlin Vmin Vlin Vmin
G1
40° Pitch
17 3.89/ 2.37/ 2.44/ 1.50/ 1.83/ 1.22/
G2
30° Pitch
21 4.86/ 2.76/ 2.77/ 2.00/ 2.32/ 1.60/
G3
20° Pitch
26 5.51/ 2.95/ 3.07/ 2.38/ 2.67/ 1.71/
G4
15° Pitch
35 7.12/ 4.70/ 4.61/ 3.46/ 3.66/ 2.67/
G5
10° Pitch
44 8.43/ 5.57/ 5.83/ 4.23/ 4.32/ 3.43/
G6
5° Pitch
53 7.44/ N/A 6.75/ N/A 6.10/ N/A
 
All values in the above table are approximate and depend on the density of the fluid. Accuracy in both the linear and non-linear ranges may be improved by using the advanced curve-fitting techniques present in one of EMCO's flow processors or the EZ-Logic™ electronics. Consult EMCO if your application fails outside the above limits.
 
Vmax = maximum velocity of fluid [ft/sec (m/sec)]
Vlin = minimum velocity of fluid at which rotor response is linear [ft/sec (m/sec)]
Vmin = minimum measurable velocity of fluid [ft/sec (m/sec)]
p = density of fluid [lb/ft3 (kg/m3)]

Back to top

Physical Specifications
Materials Wetted parts Blades: ten blade, precision-machined housing: 316 stainless steel
Pivot: tungsten carbide
Rotor bearing type Liquid: CSJ stellite jewel
Gas or steam: DEV tungsten carbide
Wetted parts 316L stainless steel stem and housing (bronze and carbon steel housing on Tubo-Bar 600/60S)
External parts Aluminum, 316 stainless steel, carbon steel (bronze and carbon steel on 600 and 900 series)
Electrical enclosure 383 Aluminum: approved for NEMA 4X for water-tight and dust-tight requirements.
Sensor Electromagnetic pick-up, 10 mV peak to peak min, 330Ω nominal resistance
Process connection TMP-600/60S 2" NPT
TMP-700 2" NPT or 2" 150#, 300#, 600#, or 900# ANSI raised face flange
TMP-910/960 2" NPT or 2" 150#, 300#, 600#, or 900# ANSI raised face flange
Isolation valve
(TMP-600/60S only)
2" full-port bronze gate valve, 125 psi (8.62 bar) max
Pressure tap and bleed valve Standard 1/4" NPT pipe nipple with 1/4" stainless steel bleed valve provides connections for mounting optional pressure transmitter (Model PT) (bleed valve is bronze for Turbo-Bar-600/60S only)
Model PT pressure transmitter(optional) A pressure transmitter can be mounted using the 1/4" NPT connection on the bleed valve supplied with the meter, eliminating the need for a separate pressure tap. A 4 to 20 mA output, scaled to the desired pressure range, is provided.
Temperature sensor
(RTD optional)
A 1000Ω, 3-wire, platinum RTD can be mounted inside the stem of the meter probe, eliminating the need for a separate termperature tap.
Temperature transmitter
(TXX optional)
Includes the RTD option with an additional 4 to 20 mA output, scaled to the desired temperature range.
Mounting standard Transmitter integrally mounted on sensor
Option Transmitter remote mounted (only available with EZ-Logic electronics option)
Approvals FM Class I, Division 2, Groups A, B, C, & D Class II, III, Division 2, Groups F & G
(Not available with 4 to 20 mA temperature transmitter)
European CE Mark European CE Mark when used with EZ-Logic electronics and without 4 to 20 mA temperature output.

Back to top

Installation
Installation Specifications
Tap size 1.875" (47.6 mm) minimum diameter
Mounting Install flow meter vertically, horizontally, or at any angle. The meter is attached perpendicular to the axis of the pipe and should not be mounted upside-down (with its top section hanging below the pipe mount). For liquid service, the flow line must be full during flow meter operation. In vertical lines, flow direction should be upward for optimum flow meter performance.
Straight run piping (D = internal diam. of pipe) Upstream Downstream
One 90° elbow before meter 10 D 5 D
Two 90° elbows before meter 15 D 5 D
Two 90° elbows out of plane before the meter 30 D 5 D
Reduction before the meter 10 D 5 D
Regulator or valve partially closed before the meter 30 D 5 D
Site selection Select installation location to minimize turbulence and swirl. The piping configuration, (i.e., values, elbows, pumps) may add disturbances to the flow.
Hot-tap compatibility The TMP-600/60S is hop-tap compatible, which means that the sensor can be installed and removed under full-flow conditions. The TMP-800/80S with flanged connection and TMP-910/960 are hot-tap compatible when installed with a 2" double flanged, full-port ball, or gate valve.

Back to top

Model Codes
Model Codes
Category Description Suffix Codes
Model Liquid or gas service 400°F (204°C) 600 - - - -
Steam service 400°F (204°C) 60S - - - -
Liquid, gas, or steam service 600°F (316°C) 700 - - - -
Liquid, gas, or steam service 400°F (204°C) 910 - - - -
Liquid, gas, or steam service 750°F (400°C) 960 - - - -
Connection 2", male NPT (Model 700) - 2NPT - - -
2" 150# flange (Model 700, 910, 960) - 2F150 - - -
2" 300# flange (Model 700, 910, 960) - 2F300 - - -
2" 600# flange (Model 700, 910, 960) - 2F600 - - -
2" 900# flange (Model 700, 910, 960) - 2F900 - - -
2" 1500# flange (Model 910, 960) - 2F1500 - - -
Thread-o-let xx = 03 to 80" (Models 600/60S) includes 2" isolation valve - VXX - - -
Rotor Liquid 30ft/sec (9 m/sec) max (40° pitch) - - L1 - -
Gas or steam, 55ft/sec  (17 m/sec) max (40° pitch) - - G1 - -
Gas or steam, 70ft/sec (21 m/sec) max (30° pitch) - - G2 - -
Gas or steam, 85ft/sec (26 m/sec) max (20° pitch) - - G3 - -
Gas or steam, 115ft/sec (35 m/sec) max (15° pitch) - - G4 - -
Gas or steam, 145ft/sec (44 m/sec) max (10° pitch) - - G5 - -
Gas or steam, 175ft/sec (53 m/sec) max (5° pitch) - - G6 - -
Electronics EZ-Logic™ with local rate and total3 - - - LOC-TOT -
Remote, only available with LOC-TOT - - - RMT -
FM approval5 - - - FM -
Pressure Transmitter No pressure transmitter - - - - XX

PT for pressure range 0 to 50 psig (0 to 3.44 barg)

- - - - 50
0 to 100 psig (0 to 6.89 barg) - - - - 100
0 to 150 psig (0 to 10.34 barg) - - - - 150
0 to 200 psig (0 to 13.79 barg) - - - - 200
0 to 250 psig (0 to 17.24 barg) - - - - 250
0 to 500 psig (0 to 34.47 barg) - - - - 500

TMP-910-2F900-G3-LOC-TOT-0200-T12-E1 represents a model TMP-910 insertion turbine flow meter for liquid, gas, or steam service with a 2" 900# flange, a 20° pitch rotor with 85 ft/sec (26 m/sec) maximum measurable velocity, EZ-Logic™ with local rate and total, a pressure transmitter scaled to 0 to 200 psig (0 to 13.79 barg), a temperature sensor and transmitter scaled to 212 to 400°F, and a one-foot stem extension.

Notes:

  1. The G6 is the only available 1" shrouded rotor.
  2. Not available with European CE Mark
  3. Unit directional flow only. Unit has 4 to 20 mA and frequency output.
  4. Remote mount electronics are required for high process temperatures. The standard remote option comes with 30' of cable.
  5. Certified by FM for Class I, Div. 2, Groups A,B,C, & D; Class II, III, Div. 2, Groups F & G; NEMA 4X. Not approved by FM when using a 4 to 20 mA temperature transmitter or a 110/220 VAC power supply option. If FM is required, use RTD option only for temperature selection.
  6. Special transmitter scaling is available. Please note scaling range below Model codes when ordering. If no special scaling is indicated, transmitter will be scaled per Model code.
Back to top